Momentum Modbus Plus 170 PNT Series Guide de l'utilisateur Page 166

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 376
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 165
Using the I/O Bus Port
166
870USE10110 July 2004
Network Status Indication in the M1 Ethernet Module
Overview The M1 Ethernet Module can provide I/O bus network status via the Module Status
function in the programming panel or by a STAT element in user logic. The fourth
word of the status element contains information regarding the integrity of the
network.
Operation The I/O bus status word contains a valid value only when the processor is running.
A zero value indicates that normal I/O bus communication is occurring.
A non-zero value indicates a problem.
Failure
Indication
If there is a communications error, bit values in the I/O bus status word contain
information on the failure mode, as follows.
Status
Word
Values
Description
Bits 0 - 14 These bits contain a value from 1 to 255, signifying the network position of the
module that cannot be reached. For example, a value of 8 indicates a
communications failure in accessing the 8th module on the network.
Bit 15 This bit contains a value of 0 or 1.
A value of zero indicates a general communication failure, for example, no power
to the module or a break in its input cable.
A value of 1 indicates that communication is possible, but the I/O bus ID received
from the module does not match the module type contained in the traffic cop for
that position.
Vue de la page 165
1 2 ... 161 162 163 164 165 166 167 168 169 170 171 ... 375 376

Commentaires sur ces manuels

Pas de commentaire