Configuring an M1 CPU with Modsoft
200
870USE10110 July 2004
Changing the Modbus Address for Modbus Communication Ports for
Momentum Components Using Modsoft
Overview Each port can be assigned a Modbus network address in the range 1...247. That
address must be unique with respect to all other device addresses on the same
Modbus networks.
Since Modbus port 1 and Modbus port 2 are always on different Modbus networks,
they can both be assigned the same address value without conflict. The factory-set
default for both ports is address 1.
Procedure From the port editor screen, perform the steps in the following table to change the
Modbus address:
Step Action
1 Place the cursor on the current address entry for the Modbus port.
2 Type a number in the range 1...247. Push <Enter>.
Result: The Port editor screen is updated with the address number you have typed,
and the cursor moves to the delay column.