Configuring a Modbus Plus Network in Modsoft with Peer Cop
870USE10110 July 2004 231
Completing the I/O Device Configuration in Peer Cop
Introduction Using the procedures described previously, you can complete the I/O configuration
in Peer Cop. This section shows completed Peer Cop screens for this example.
Register
Assignments
For this example, we have made the following register assignments:
Completed
Screen: Node 2
The completed Peer Cop screen for node 2 should look like this:
MB+ Address Device Type Register Assignment
2 16-point discrete input 300016
3 16-point discrete output 400016
4 32-point discrete input 300017 and 300018
5 32-point discrete output 400017 and 400018
Utility
GoToNode
AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 240 ms Total Links: Link Id:1
PEER COP
On Error : HOLD USED 13 OF 1366 WORDS
REFERENCE LEN TYPE INDEXMODE
F2
Timeout
Access to Node : 2
TO ALL NODES ON LINK
GLOBAL OUTPUT -
DelNode
SPECIFIC INPUT 300016-300016 1 BIN
SPECIFIC OUTPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -