Configuring a Modbus Plus Network in Concept with Peer Cop
318
870USE10110 July 2004
Devices on the Network
Introduction This section describes the five devices which comprise the sample network and the
strategy used to assign addresses.
Procedure The following table list the Modbus plus address and components of each TSX
module on the network.
Address
Strategy
In this type of architecture, assign the lowest network address (1) to the CPU. When
the network initializes, the CPU will be the first device to get the token, and the token
rotation table will be built with respect to the controlling device on the network.
Modbus Plus
Address
I/O Base Type Adapter Type
1 (type not
specified)
M1 processor adapter (type not specified)
172 PNN 210 22 Modbus Plus option adapter
2 170 ADI 340 00
16-point input
170 PNT 110 20 Modbus Plus communication adapter
3 170 ADO 340 00
16-point output
170 PNT 110 20 Modbus Plus communication adapter
4 170 ADI 350 00
32-point input
170 PNT 110 20 Modbus Plus communication adapter
5 170 ADO 350 00
32-point output
170 PNT 110 20 Modbus Plus communication adapter