Using Peer Cop with Modsoft
194
870 USE 101 00 V.2.2
Accessing the Peer Cop Configuration Extension Screen,
Continued
Estimating How
Much Memory to
Reserve
Follow these guidelines for estimating the amount of extension memory you will
need for your Peer Cop database:
For... Add... Up to a maximum of...
Overhead 9 words --
Global output 5 words --
Global input number of words=
number of devices x
(1 + 2 x number of device subentries)
1088 words
Specific output 2 words for every device entry in Peer Cop 128 words
Specific input 2 words for every device entry in Peer Cop 128 words