Momentum Modbus Plus 170 PNT Series Guide de l'utilisateur Page 251

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 373
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 250
Saving to Flash in Modsoft
870 USE 101 00 V.2.2
239
Saving to Flash
Conditions for
Saving to Flash
In order to save the application program and state RAM values to Flash:
The Modsoft panel must be Online
The PLC must be stopped (not solving logic)
Save-to-Flash
Procedure
Follow the steps below to save to Flash.
Continued on next page
Step Action
1 With the PLC online, go to the Ladder Diagram editor or the Segment Status
Display.
2 From the PlcOps pulldown on the top menu, select
Save to Flash
.
Result:
If the PLC is stopped when you select
Save to Flash
, the following screen
appears:
3 Answer the first two questions to specify the way you want the PLC to restart after a
power-down.
Vue de la page 250
1 2 ... 246 247 248 249 250 251 252 253 254 255 256 ... 372 373

Commentaires sur ces manuels

Pas de commentaire