TIO Power Supply Module
870 USE 101 00 V.2.2
355
External Operating Voltage Connections,
Continued
Grounding
The spade-lug connector on the front of the module provides a short, secure PE
grounding surface.
Electrical safety
Power supply modules may not be operated in parallel. Physically separate input
cabling from output cabling.
Fusing
Dimension the F1 fuse to match the operative load, observing the minimum values
in the following table:
Voltage Jumper Placement External Fusing (min. F1)
120 VAC Mounted 0.63 A slow-blow
230 VAC Removed 0.315 A slow-blow