Using Peer Cop with Concept
312
870 USE 101 00 V.2.2
Specifying References for Input and Output Data,
Continued
Defining the
Global Inputs,
Continued
Next Step
Defining the references for the next node.
Step Action
3 Type the value
1
in the Index column, indicating that the CPU will receive part of
the global input data beginning with the first word.
4 Type the value
5
in the Length column, indicating that the CPU will accept five
words of the global input data. Leave the default
BIN
setting.
5 Click
<OK>
.